Specifications for High Rate Unconventional Water Treatment Plant

Ref: Schedule of Rates, MJP, Pune Region, 2012-2013

Designing (aesthetically), providing and constructing  high  rate  Unconventional Water  Treatment  Plant  i.e.  Simplified Water  Treatment  Plant  consisting  of Civil,  Mechanical  and  Electrical  works including cost of providing and applying epoxy paint to inside surface of water retaining   structures   in   contact   with chlorine   and   providing   anti-termite treatment   to   entire   structure  below ground level, mechanical and electrical components  of  various  sub-works  as given    below,    including    necessary hydraulic testing, structural testing and trial run for 3 months, etc. complete as directed  by  Engineer-in-charge  (turn- key job) works.
1)  Aeration fountain
2)  Inlet arrangements
3)  Mixing channel with ventury flume and  flow measuring arrangement
4)  Inlet channel
5)  Flocculator  - Conforming to I.S.  7208-1974 (Type-C) with detention period of 30 minutes
6)  Tube  settlers - Designing,  fabricating and  constructing  Tube  Settlers  with square  or  any  other  shaped  tube  like Circular,  Cheveron,   Hexagonal   etc.having proven performance.
7) Rapid sand gravity filters
8) Filter house
9) Chemical house
10)Alum  tanks  2  Nos.  with  mixing,   carrying and dosing arrangements with piping.
11)   Gravity feed gas chlorinator with 100%    standby.
12)   TCL solution tank with mixing, carrying    and dosing arrangement with piping.
13) Bypass arrangement
14) External and internal electrification
15) Laboratory equipments
16) Wash water tanks of capacity equal to 2% of designed quantity of filtered water     in a day (+)10%.
 17)  Wash water pumps with 100% standby.
18)  Air  blowers  capable  of  delivering  600  LMP per square metre of free air of filter
area  at   0.4  Kg/  sqcm  at  the  under  drains (100% standby).
19) Pure water sump of capacity equal to 1  hour pumping capacity.
20)     Pure water pump house over the sump / by the side pump.
21)    Drainage arrangements
22)     Alum store
23)  Sanitary  block  with  necessary  water   supply and drainage arrangements and   internal WBM roads.
24)   These rates are applicable for seismic  zones 2, 3 and 4.
25)      Rates given below are inclusive of uplift   pressure if any and dewatering during     the entire work.
26)  All RCC structures shall be constructed  in M-300.
27)     Unconventional  Treatment  Plants  less than   1  MLD  capacity  shall  not  be
constructed.
Note : Conditions from Sr. No. 1 to 27 shall  form  a  part  and  parcel  of  the tender  and  must  be  included  in  draft tender   papers   for   the   work   of unconventional treatment plants.

Pin It